壹、用(yong)途(tu)
高(gao)壓(ya)電(dian)纜(lan)外(wai)護套故(gu)障測試(shi)儀(yi)是(shi)基(ji)於(yu)MURRAY電(dian)橋(qiao)原(yuan)理而(er)設(she)計的,可(ke)用(yong)於(yu)敷設(she)後(hou)各種(zhong)電(dian)線(xian)電(dian)纜(lan)的擊穿(chuan)點(dian)及(ji)沒(mei)有擊(ji)穿但絕緣(yuan)電(dian)阻(zu)值偏(pian)低的缺陷(xian)點(dian)的定位(wei)。當然,也可(ke)用(yong)於(yu)電(dian)纜(lan)廠內各種(zhong)線(xian)纜的缺陷(xian)點(dian)定(ding)位(wei)。
設(she)備采用(yong)開(kai)關(guan)電(dian)源(yuan)構(gou)成高(gao)壓(ya)恒流(liu)源(yuan),空載(zai)電(dian)壓(ya)7500V,短路(lu)電(dian)流(liu)40mA,采(cai)用(yong)高(gao)靈敏度放(fang)大器(qi)及(ji)檢(jian)流(liu)計指示(shi)平(ping)衡(heng),與(yu)比(bi)例電(dian)位(wei)器(qi)構(gou)成平(ping)衡(heng)電(dian)橋(qiao),整(zheng)體(ti)置(zhi)於(yu)高(gao)電(dian)位(wei),測量(liang)電(dian)纜(lan)為特(te)別設(she)計的雙芯(xin)高(gao)壓(ya)橡皮(pi)電(dian)纜(lan),用四端(duan)電(dian)阻(zu)測量(liang)法(fa)避免了(le)引(yin)線(xian)電(dian)阻(zu)引(yin)入(ru)的誤差,電(dian)纜(lan)通(tong)過編(bian)織(zhi)屏蔽層(ceng)可(ke)靠(kao)接(jie)地,面(mian)板(ban)上的操(cao)作(zuo)鈕(niu)處(chu)於(yu)低電(dian)位(wei),通(tong)過絕(jue)緣(yuan)桿(gan)操(cao)作(zuo)電(dian)橋(qiao)。高(gao)壓(ya)恒流(liu)源(yuan)和(he)電(dian)橋(qiao)集成在壹(yi)個便(bian)攜式鋁合金(jin)箱(xiang)內。因此(ci),該設(she)備電(dian)壓(ya)高(gao)、重量(liang)輕、操(cao)作(zuo)方便、使用安全(quan)。
與(yu)波(bo)反射法相比(bi),電(dian)橋(qiao)平(ping)衡(heng)法(fa)沒(mei)有盲區,特(te)別適(shi)用於(yu)判斷短電(dian)纜(lan)及(ji)靠(kao)近(jin)端頭的擊穿(chuan)點(dian),操(cao)作(zuo)容易。
高(gao)壓(ya)電(dian)纜(lan)外(wai)護套故(gu)障測試(shi)儀(yi)特(te)別適(shi)用於(yu)
1、敷設(she)後(hou)電(dian)纜(lan)的高(gao)阻(zu)擊穿(chuan)點(dian),特(te)別是(shi)難以燒(shao)成(cheng)低阻(zu)的線(xian)性高(gao)阻(zu)擊穿(chuan)點(dian),如(ru)電(dian)纜(lan)中(zhong)間(jian)接頭的線(xian)性高(gao)阻(zu)擊穿(chuan)。
2、閃(shan)絡(luo)型(xing)擊穿(chuan)點(dian),擊(ji)穿(chuan)後(hou)恒流(liu)源(yuan)能(neng)維(wei)持(chi)電(dian)弧,有(you)穩(wen)定(ding)電(dian)流(liu)通(tong)過電(dian)橋(qiao),電(dian)橋(qiao)有足夠(gou)的靈敏度。
3、尚(shang)未擊穿,但電(dian)阻(zu)偏低的缺陷(xian)點(dian),如(ru)用兆(zhao)歐表(biao)發(fa)現(xian)電(dian)纜(lan)阻(zu)值較低,但運(yun)行(xing)電(dian)壓(ya)下不擊穿(chuan)的絕緣(yuan)缺(que)陷(xian)點(dian)。
由於(yu)上述(shu)特(te)點(dian),高(gao)壓(ya)電(dian)纜(lan)外(wai)護套故(gu)障測試(shi)儀(yi)特(te)別適(shi)合以下用戶:
從事專(zhuan)業(ye)定位(wei)的隊伍(wu):如(ru)大中(zhong)型(xing)供電(dian)局(ju)及(ji)大(da)型(xing)用電(dian)企(qi)業(ye)的電(dian)纜(lan)修試(shi)班(ban)。絕(jue)大(da)部分(fen)的電(dian)纜(lan)擊穿點(dian)均(jun)可(ke)用(yong)本儀(yi)器(qi)迅速(su)找到(dao)大致(zhi)的擊穿(chuan)位(wei)置(zhi)。與波(bo)反射(she)法(fa)及(ji)定(ding)點(dian)儀(yi)配(pei)合(he)使用,取長(chang)補(bu)短(duan),使定位(wei)更(geng)快更(geng)可(ke)靠(kao)。
1、小(xiao)型(xing)用戶:如(ru)小型(xing)供電(dian)局(ju)及(ji)中(zhong)型(xing)用電(dian)企(qi)業(ye)。電(dian)纜(lan)不多,壹(yi)般(ban)走向清楚,不太長(chang),故(gu)障次(ci)數有(you)限,若(ruo)配齊(qi)壹套波(bo)反(fan)射(she)法定位(wei)儀,價格高(gao),對(dui)使用(yong)人(ren)員(yuan)的素質和(he)經驗要(yao)求(qiu)較高(gao)。選用本儀(yi)器(qi)測試(shi)儀(yi)操(cao)作(zuo)方便,能應(ying)付(fu)日(ri)常需要(yao),是(shi)較好的辦(ban)法(fa)。
2、電(dian)纜(lan)生產廠(chang):在廠(chang)內,可(ke)用(yong)作(zuo)各種(zhong)線(xian)纜擊(ji)穿點(dian)的定位(wei),選配數(shu)字(zi)電(dian)容(rong)表(biao),可(ke)找出斷線(xian)點(dian)。該設(she)備重量(liang)輕,便於(yu)攜帶(dai)至現(xian)場為電(dian)纜(lan)用戶作定(ding)位(wei)服務。
二、技術指標(biao)
1.空載(zai)電(dian)壓(ya) ≥7500V
2.短路(lu)電(dian)流(liu) ≥40mA
3.定(ding)位(wei)比(bi)例精(jing)度±(0.2%·L±1)米
4.重量(liang) 3.5kg
5.工(gong)作(zuo)電(dian)源(yuan): 220V
電(dian)話(hua)
微(wei)信(xin)掃壹(yi)掃