密(mi)集型(xing)耐火母(mu)線槽(cao)是壹(yi)種(zhong)專(zhuan)為高層建築(zhu)及重(zhong)要(yao)設(she)施(shi)設(she)計(ji)的(de)輸(shu)配電(dian)設(she)備(bei),具備(bei)優(you)良(liang)的耐火與(yu)絕(jue)緣(yuan)性(xing)能(neng)。其結構(gou)采(cai)用“三明治”式(shi)緊密(mi)疊(die)壓(ya)設(she)計(ji),導體(ti)由(you)耐火雲(yun)母(mu)帶包(bao)纏,外殼(ke)為冷成(cheng)型(xing)薄(bo)鋼(gang)型(xing)材(cai),表(biao)面鍍(du)鋅並噴塗防火(huo)塗料(liao),遇火時能(neng)迅(xun)速膨脹(zhang)形(xing)成(cheng)致密(mi)隔(ge)熱(re)層(ceng),有(you)效(xiao)阻(zu)止(zhi)高溫氣體(ti)侵(qin)入(ru)。內(nei)部(bu)支架(jia)采(cai)用耐火絕(jue)緣(yuan)材(cai)料(liao),固(gu)定母(mu)線並(bing)增強(qiang)結構(gou)穩定性(xing)。
該(gai)母(mu)線槽(cao)適(shi)用於(yu)額(e)定電(dian)壓(ya)690V以(yi)下(xia)、電(dian)流250-5000A的輸(shu)配(pei)電(dian)系(xi)統(tong),可在失(shi)火(huo)環境(jing)中連(lian)續(xu)運行(xing)1小時以上(shang),確(que)保消(xiao)防設(she)備(bei)、應(ying)急(ji)照(zhao)明(ming)等(deng)關(guan)鍵(jian)負(fu)載的持(chi)續供(gong)電(dian)。其母(mu)線系(xi)統溫(wen)升(sheng)控(kong)制(zhi)嚴格(ge),連(lian)接端(duan)子(zi)溫(wen)升不超過60K,外殼(ke)不超過30K,絕(jue)緣(yuan)件(jian)表(biao)面不超過40K,確(que)保長(chang)期運(yun)行(xing)的可靠(kao)性(xing)。接頭(tou)采用專(zhuan)用耐火絕(jue)緣(yuan)組(zu)件(jian),連(lian)接可靠(kao)且便(bian)於(yu)維(wei)護。
1、彈(dan)線定位(wei):根(gen)據設(she)計(ji)圖(tu)紙(zhi)和施工(gong)現(xian)場的(de)實際(ji)情(qing)況(kuang),準(zhun)確(que)彈(dan)出(chu)母(mu)線槽(cao)的安裝中心(xin)線和標(biao)高(gao)控制(zhi)線,以(yi)確(que)定母(mu)線槽(cao)的安裝位(wei)置(zhi)和走(zou)向,確(que)保安裝後(hou)的母(mu)線槽(cao)整齊(qi)、美觀、符合(he)設(she)計(ji)要(yao)求(qiu)。
2、支架(jia)安裝:
支架(jia)選型(xing):根(gen)據母(mu)線槽(cao)的重(zhong)量(liang)、長(chang)度(du)、電(dian)流大小等因(yin)素(su)選擇合(he)適(shi)的支架(jia)型(xing)號和材質,確(que)保支架(jia)具有(you)足(zu)夠(gou)的(de)承載能力和穩定性(xing)。
安裝位(wei)置(zhi):支架(jia)的(de)安裝位(wei)置(zhi)應(ying)準(zhun)確(que)無(wu)誤,間距(ju)應(ying)符(fu)合(he)設(she)計(ji)要(yao)求(qiu),壹(yi)般(ban)水平(ping)安裝時(shi)相鄰(lin)支架(jia)間距(ju)不應(ying)大(da)於(yu)2m,垂直安裝時(shi)支架(jia)間距(ju)不應(ying)大(da)於(yu)3m,在母(mu)線槽(cao)的彎(wan)頭(tou)、三通(tong)、四(si)通(tong)等(deng)特殊(shu)部(bu)位(wei)應(ying)適(shi)當增(zeng)加(jia)支架(jia)數(shu)量(liang)。
固(gu)定方(fang)式:支架(jia)應(ying)牢(lao)固(gu)地(di)固(gu)定在建築(zhu)物的結構(gou)上(shang),如墻體(ti)、樓(lou)板、梁(liang)等,可采(cai)用膨脹(zhang)螺(luo)栓、焊接等(deng)方(fang)式進(jin)行(xing)固(gu)定,但不得損(sun)傷(shang)建築(zhu)物的結構(gou)強(qiang)度(du)。在混凝(ning)土(tu)結構(gou)上(shang)安裝支架(jia)時(shi),膨脹(zhang)螺(luo)栓的埋入(ru)深度(du)和拉力值應(ying)符(fu)合(he)相關標(biao)準(zhun)要(yao)求(qiu);在鋼(gang)結構(gou)上(shang)安裝支架(jia)時(shi),應(ying)采(cai)用焊接或專(zhuan)用夾(jia)具進(jin)行(xing)固(gu)定,並確(que)保焊縫質量。
3、母(mu)線槽(cao)安裝:
水平(ping)安裝:將(jiang)母(mu)線槽(cao)按(an)照(zhao)順(shun)序依次放(fang)置在支架(jia)上(shang),使用連(lian)接螺(luo)栓將各(ge)段母(mu)線槽(cao)連(lian)接成(cheng)整(zheng)體,擰緊螺(luo)栓時應(ying)采(cai)用扭矩扳手,確(que)保螺(luo)栓的擰(ning)緊力矩符合(he)規(gui)定要(yao)求(qiu),防止(zhi)螺(luo)栓松動(dong)。在連(lian)接過程(cheng)中,要(yao)註(zhu)意(yi)保(bao)持(chi)母(mu)線槽(cao)的水平(ping)度(du)和直線度(du),相鄰(lin)段母(mu)線槽(cao)之間的(de)連(lian)接縫(feng)隙應(ying)均(jun)勻(yun)壹(yi)致,不得有(you)明(ming)顯錯縫(feng)。
垂直安裝:垂直安裝母(mu)線槽(cao)時,壹(yi)般(ban)從下(xia)到(dao)上(shang)逐段(duan)進(jin)行(xing)安裝,先(xian)在底(di)部(bu)安裝固(gu)定好起(qi)始(shi)段(duan)母(mu)線槽(cao),然(ran)後(hou)依次(ci)向(xiang)上(shang)吊(diao)裝和連(lian)接各(ge)段母(mu)線槽(cao)。在吊(diao)裝過程(cheng)中,要(yao)註(zhu)意(yi)防止(zhi)母(mu)線槽(cao)晃動(dong)和碰撞,可使用吊(diao)車、葫(hu)蘆等(deng)起(qi)重(zhong)設(she)備(bei)配(pei)合(he)作(zuo)業,並(bing)安排專(zhuan)人(ren)在壹(yi)旁(pang)進(jin)行(xing)輔助(zhu)和監護(hu)。垂直安裝的(de)母(mu)線槽(cao)應(ying)設(she)置(zhi)防晃(huang)支架(jia)或夾(jia)具,以防止(zhi)母(mu)線槽(cao)因(yin)自重(zhong)而產生晃(huang)動(dong)或位(wei)移(yi)。
連(lian)接部(bu)位(wei)處理:母(mu)線單元(yuan)之(zhi)間進(jin)行(xing)連(lian)接時(shi),必須(xu)保持(chi)連(lian)接裝(zhuang)置的表(biao)面清(qing)潔,並(bing)且(qie)母(mu)線管(guan)在同壹(yi)條(tiao)直線上(shang),然(ran)後(hou)擰緊螺(luo)栓。擰緊連(lian)接器後,用油(you)漆(qi)筆標(biao)記(ji)以確(que)認擰(ning)緊。對於(yu)插(cha)接箱(xiang)等(deng)分支連(lian)接部(bu)位(wei),要(yao)確(que)保插(cha)接箱(xiang)的(de)安裝位(wei)置(zhi)準(zhun)確(que),與(yu)母(mu)線槽(cao)的連(lian)接緊密(mi)可靠(kao),插(cha)接箱(xiang)內(nei)的(de)開關設(she)備(bei)應(ying)處於(yu)斷開(kai)狀態,並在安裝完成(cheng)後(hou)進(jin)行(xing)絕(jue)緣(yuan)測試。
4、防火(huo)封堵(du)與(yu)防護(hu):
防火(huo)封堵(du):在母(mu)線槽(cao)穿(chuan)越防火(huo)墻、樓(lou)板等防火(huo)分區(qu)處,應(ying)采(cai)用防火(huo)封堵(du)材(cai)料(liao)對縫隙進(jin)行(xing)封堵(du),如(ru)防火(huo)泥、防火(huo)枕等(deng),以防止(zhi)火災(zai)蔓延(yan)時(shi)火(huo)勢通(tong)過母(mu)線槽(cao)蔓延(yan)至(zhi)其他(ta)區域(yu),確(que)保防火(huo)分區(qu)的完整性(xing)。
防護(hu)措施(shi):在母(mu)線槽(cao)安裝完成(cheng)後(hou),應(ying)對(dui)其采取防護(hu)措施(shi),防止(zhi)異物侵入(ru)和機械(xie)損(sun)傷(shang)。可在母(mu)線槽(cao)上(shang)覆蓋(gai)防護(hu)蓋板或防護(hu)網,在易(yi)受碰(peng)撞的(de)部(bu)位(wei)設(she)置(zhi)防撞護(hu)欄或警(jing)示(shi)標(biao)誌(zhi)。對(dui)於(yu)安裝在室外或潮(chao)濕環(huan)境中的(de)母(mu)線槽(cao),還(hai)應(ying)采(cai)取防水、防潮(chao)措施(shi),如(ru)設(she)置(zhi)防水彎(wan)、加(jia)裝(zhuang)防水罩(zhao)等。